1、 摘要摘 要本工程为某市某小区供热管网及换热站设计。小区内所有建筑物均为民用住宅,四周为商业网点。小区占地面积约为12万平方米,建筑面积约为15万平方米。供暖热负荷6762.53kw,总循环水量232.63t/h。小区一次水供回水温130℃/80℃,二次水供回水温95℃/70℃。管网布置为闭式双管异程式系统,枝状形式。采用补水泵定压方式,系统运行时,采用质调节调节方式,以适应热负荷的变化。整个管道均为直埋敷设,采用方形补偿器进行补偿,所有管段采用预制保温管,保温材料为聚氨酯,保护层为高密度聚乙烯,由国家标准设计图集《管道及设备保温》98R418确定其保温层厚度,通过水力计算确定管径。小区设一个换热站,内设2台型号BR0.5板式换热器,2台型号为ISW200-250的热水循环泵(一备一用),2台型号为IS50-32-125的补水泵(一备一用),一个补给水箱的型号为YXDY-2000.一台软。

2、水器的型号为180-WS-3072。整个网路由绘制的水压图可知网路压力工况均满足技术要求。关键词: 热负荷;水压图 ;热力交换站;质调节I AbstractAbstractThis project is in mou City district heating network and heat transfer station design. All the buildings are in the residential district, surrounded by commercial outlets. Residential area of ​​approximately 120,000 square meters, construction area of ​​about 150,000 square meters. Heating load 6762.53kW, total c。

3、irculating water 232.63t / h.A water supply and return water temperature of the cell 130 ℃ / 80 ℃, the secondary water supply and return water temperature is 95 ℃ / 70 ℃. Network Layout is a closed two-pipe return system, dendritic form. Using up water pumps constant pressure mode, the system is running, adjust the way qualitative adjustment to accommodate thermal load changes. Buried pipes are ou。

4、tstanding throughout, with square compensator to compensate all pipe sections prefabricated pipe insulation, polyurethane insulation materials, protective layer of glass and steel, designed by the national standards Atlas "pipe and equipment insulation" 98R418 determine its insulation thickness, diameter is determined by hydraulic calculation. Set up an underground cell heat transfer stations, and。

5、 offers 2 models BR0.5 plate heat exchanger, two model ISW200-250 hot water circulation pump (a preparation of a use), 2 sets of model IS50-32-125 supply pump (a preparation of a use), horizontal through decontamination. Water pressure throughout the network by the drawing figure shows network pressure conditions are meet the technical requirements.Keywords: thermal load; hydraulic diagram; heat e。

6、xchange station; quality regulationII 目录目录第1章 绪论 11.1工程概况 21.2方案的确定 21.2.1供热方案的确定 21.2.2敷设方式的确定 31.2.3换热站的确定 31.3设计内容 4第2章设计依据及原始资料 52.1原始资料 52.1.1基本资料 52.1.2土建资料 52.1.3热源资料 52.2设计依据 5第3章 集中供热系统的热负荷 73.1 集中供热系统热负荷的概算 73.2 热负荷的计算 7第4章 供热方案的确定及管道布置 124.1供热方案的确定 124.1.1供热方案确定原则 124.1.2供热方案的确定 124.2热网系统形式的选择 144.3供热管线的敷设与构造 154.3.1供热管网布置原则 154.3.2敷设方式的选择 154.3.3供热管道及其附件 164.3.4供热管道的保温 184.3.5补偿器的选择 20。

7、4.3.6固定支座的位置确定 22第5章 水力计算 235.1 水力计算的方法及步骤 235.2各设计流量的确定 235.3主干线水力计算 245.4支线水力计算 24第6章 水压图的绘制与热网连接方式的确定 256.1水压图的绘制 256.1.1热水网路压力状况的基本技术要求 256.1.2绘制热水网路水压图的步骤: 256.2连接方式的确定 27第7章 换热站的形式选择及计算 297.1换热站的形式选择 297.2换热站的内部设备计算 307.2.1换热器的计算和选择 307.2.2循环水泵的计算和选择 347.2.3补给水泵的计算和选择 357.2.4补水箱的选择 387.2.5软水设备的选择 397.2.6除污器的选择 39第8章 热水供热系统的供热调节 418.1供热调节 418.2直接连接质调节计算 41第9章 技术经济分析 43第10章 结论 44参考文献 45附录一 46致。

8、 谢 56IV 绪论第1章 绪论集中供热是指以热水或蒸汽作为热媒,由一个或多个热源通过热网向城市、城镇或其中某些区域热用户供应热能的方式。目前已成为现代化城镇的重要基础设施之一,是城镇公共事业的重要组成部分。集中供热系统由热源、热网和用户三部分组成。热源主要是热电站和区域锅炉房(工业区域锅炉房一般采用蒸汽锅炉,民用区域锅炉房一般采用热水锅炉),以煤、重油或天然气为燃料;有的国家已广泛利用垃圾作燃料。工业余热和地热也可作热源 。核能供热有节约大量矿物燃料,减轻运输压力等优点。热网分为热水管网和蒸汽管网,由输热干线、配热干线和支线组成,其布局主要根据城市热负荷分布情况、街区状况、发展规划及地形地质等条件确定,一般布置成枝状,敷设在地下。主要用于工业和民用建筑的采暖、通风、空调和热水供应 ,以及生产过程中的加热、烘干、蒸煮、清洗、溶化、致冷 、汽锤和汽泵等操作。集中供热的介质主要有蒸汽、热水。其。

9、中热水介质根据温度的不同又可以分为高温循环水、低温循环水等,高温循环水一般80°C左右,而低温循环水一般温度在60°C左右。集中供热的优点是提高能源利用率、节约能源。供热机组的热电联产综合热效率可达85%,而大型汽轮机组的发电热效率一般不超过40% ;区域锅炉房的大型供热锅炉的热效率可达80%~90%,而分散的小型锅炉的热效率只有50%~60%。减少司炉人员及燃料、灰渣的运输量和散落量,降低运行费用,改善环境卫生。易于实现科学管理,提高供热质量。本设计为某市某小区供热管网及换热站施工图设计。目前,集中式供热是城市供暖的最主要方式,也是城市整体规划和布局的方向。根据小区的面积和位置,初步确定小区的热源为换热站,有依据当地的地理位置,气象,地质,海拔高度,确定热力管网的铺设方式为直埋无补偿铺设,供热调节采用分阶段改变流量的质调节。这样既满足用户热负荷的需要,又节约了能源。从而使本次设计既经济又。

10、合理,符合设计的宗旨。此次毕业设计得到了徐老师和张老师的耐心指导,及小组同学的热心帮助。为此深表感谢。由于本人的知识和能参考的资料有限,本次设计有许多不足和考虑不周到的地方,虽然在设计过程中经过各位辅导老师的细心指导,已经改正了许多错误,可还是可能存在许多纰漏之处,希望各位老师给予指正。4 第1章 绪论1.1工程概况本设计为某市某小区的供热管网及换热站设计,该小区建筑主要是居民的住宅。为了保证小区的室内温度达到满足人们生活所需要的温度,给居民提供一个舒适,安逸的居住环境,且节省资源。1.2方案的确定无论是供热方案的确定还是管道敷设方案的确定都非常重要,讲求经济节约、安全可靠、合理。1.2.1供热方案的确定集中供热系统是由热源、热网、热用户三部分组成的,向许多不同的热用户供给热能,供热范围广,热用户所需的热媒种类和参数不一,锅炉房和热电厂供给的热媒及参数往往不能完全满足所有用户的需求。因此,。

11、必须选择与热用户要求相适应的供热系统形式及其管网与热用户的连接方式。(1)热媒的确定热媒的分类:供暖系统常用的热媒是水、蒸汽、空气。供暖系统的热媒,应该根据安全、卫生、经济、建筑性质和地区供热条件等因素考虑决定。对于生产工艺负荷,通常以蒸汽为热媒。对于仅有供暖和热水供应的负荷应以热水为负荷,本设计中的建筑均为民用建筑,仅有供暖的热负荷,故可采用热水作为热媒。(2)热媒参数的确定当不具备确定最佳 供回水温度的技术经济比较条件,热水供回水温度按一下原则确定:a区域性锅炉房供回水温度区域性锅炉房为热源,供热规模较小时,供水温度可采用95/70℃,80/60℃的水温,而规模较大时,经济技术比较可用110//70℃,85/65℃、80/60℃、70/50℃。b二次网供回水温度可依据一次供回水温度和卫生要求及供热区域内热用户的需要,并经过详细的经济分析后确定。一般二次网供回水温度有如下几种参考:95/。

12、70℃、85/65℃、80/60℃、70/50℃等。本设计的集中供热系统的热源形式是以换热站为热源,提高供水温度和加大供回水温度差可使热网采用较小的管径,降低输送网路循环水的电能消耗和用户热设备的散热面积,在经济上是合理的,但是由于供水温度过高,对管道及设备的耐热要求高,运行管理水平也相应提高,综合考虑热源、热力网、热用户等方面因素并进行技术经济比较,确定本设计热媒参数为95/70℃。(3)热水系统的确定热水供热系统主要有两种形式:开式系统和闭式系统。在开式系统中,热网的循环水部分的或全部的从热网中取出,直接用于生产和热水供应热系统。在闭式系统中,热网的循环水仅作为热媒,供给用户热量而不从热网中取出。在我国,由于热水供应的负荷很小,城市供热系统的主要是并联闭式热水供暖系统。本设计热网的循环水仅作为用于供热的热媒,故采用的是闭式双管异程式系统。1.2.2敷设方式的确定热力管道的敷设分为:地上。

13、架空敷设和地下敷设。地下敷设又可以分为:地沟敷设和无地沟直埋敷设。根据地下敷设《热网规范》规定,城市街道上和居住区域内的热力管道一采用地下敷设,包括通行地沟,半通行地沟,不通行地沟,和直埋敷设。所以根据上述分析,采用直埋敷设。而且采用将供热管道、保温层、和保护层外壳三者紧密粘结在一起,形成整体的预制保温管结构。1.2.3换热站的确定集中供热系统的热力站是供热网路与热用户的连接场所,它的作用是根据热网工况和不同的条件,采用不同的连接方式,将供热管网输送的热媒加以调节、转换,向用户系统分配热量以满足用户需求,并根据需要进行集中计量,检测供热热媒的参数和流量。根据热力站的位置和功能的不同,可分为:a用户热力站—也称为用户引入口。它设置在单幢建筑用户的地沟入口或该用户的地下室或地层处,通过它向该用户或相临用户分配热能。b小区热力站—供热网路通过小区热力站向一个或几个街区的多幢建筑分配热能。这种热力。

14、站大多是单幢的建筑物,从集中热力站向各热用户输送热能的网路,通常称为二级供热管网。c街区性热力站—它用于特大型的供热网路,设置在供热主干线和分支干线的连接点处。本设计中,应用的是小区热力站。热力站设计的要求:地理位置较低,地下室或单层室内为宜;具有良好的采光条件和通风措施;净高和面积满足安装和操作要求;大型站应用大件安装孔洞,标装点及其他设备;设值班室、储备维修间、卫生间和生活间。1.3设计内容(1)热负荷计算(2)供热方案的确定(3)水力计算、根据水力计算结果绘制水压图(4)换热站的设计及内部形式的计算与选择(5)供热调节 第2章设计依据及原始资料第2章设计依据及原始资料2.1原始资料2.1.1基本资料供热参数:一次供回水温度为130/70℃,小区所有建筑物进行低温水供暖,要求供回水温度为95/70℃。其他供热参数根据外网情况确定。某市气象资料[3]:室外计算温度:-5℃冬季室外平均风速。

15、和主导风向:风速为1.5m/s采暖期天数:158天最冷月平均温度:-7℃采暖日期平均温度:-5℃最大冻土深度:133cm2.1.2土建资料该工程的总建筑面积是15万平方米,建筑物均为民用住宅,大多数是六层。每层楼高为3.6m。2.1.3热源资料该住宅小区采用集中供热的方式,热媒种类为热水,一级管网的供回水温度为95/70℃,二级管网的供回水温度为130/70℃。换热站为小区热力站,供热网路通过小区热力站向一个或几个街区的多幢建筑分配热能。这种热力站大多是单幢的建筑物,从集中热力站向各热用户输送热能的网路,通常称为二级供热管网。热力站设置在一层,在小区的西边。2.2设计依据本设计主要是根据贺平主编的《供热工程》上的集中供热系统的章节来的,根据书上的步骤首先进行负荷计算,然后进行换热方式的确定及管道敷设方式,接着进行水力计算并根据计算结果绘制出水压图和确定换热站内部换热器、水泵等的选择,最后进。

16、行了供热调节。在设计的过程中参考了以下规范: [1]李先洲,李景田等主编的暖通空调规范实施手册[2]陆耀庆主编的实用供热空调设计手册[3]邵宗义主编的建筑供热采暖工程设计图集[4]中华人民共和国建设部出版的城市热力网设计规范社,2010[5] 航天工业部第七设计研究院编的工业锅炉房设计手册[6]赵廷元等主编的热力管道设计手册[7]中华人民共和国建设部出版的城镇直埋供热管道工程技术规程57 第3章 集中供热系统的热负荷第3章 集中供热系统的热负荷3.1 集中供热系统热负荷的概算集中供热系统的热负荷是指集中供热系统所包括的各热用户热负荷之和它是供热规划和设计确定热源位置、规模、和热网布线的重要依据之一。集中供热的热用户类型比较多,主要有供热、通风、热水供应、空气调节、生产工艺等用热系统。由于对集中供热系统进行规划或初步设计时,整个区域内的各类建筑物的具体设计往往尚未进行,不可能提供较准确的建筑。

17、物热负荷的资料。因此,对不同热用户,通常是采用概算指标来确定各类热用户的热负荷。3.2 热负荷的计算(一)计算公式[1] : (3-1)式中 ---采暖设计热负荷(kW) ---采暖热指标(W/m2)---采暖建筑物的建筑面积(m2)。按我国《热网规范》给出的推荐值,见表3-1表3-1供暖面积热指标推荐值 单位:W/m2建筑物类型住宅居住区综合学校办公医院托儿所旅馆商店食堂餐厅影剧院展览厅大礼堂体育馆面积指标40~4545~5545~5555~7050~6055~70100~13080~105100~150(二)负荷计算根据《热力网设计规范》可知住宅的采暖热指标在40~45(W/m2),本小区均为居住住宅,供暖面积热指标取=43(W/m2)。A-1的负荷计算:根据CAD资料图计算单层单元面积得单元面积:A-1单元: =253×5=1265(m2)代入公式得: =43×1265/103=54。

18、.4(k W)同理计算得每个单元的负荷,填入下表3-1:表3-1 负荷计算楼编号单层面积A(㎡)层数建筑面积A(㎡)采暖热指标q(W/㎡)热负荷Qh(kw)123456A-1253512654354.40A-2187611224348.25A-3176610564345.41A-4198611884351.08A-5198611884351.08A-6198611884351.08A-7187611224348.25A-8198611884351.08A-9187611224348.25A-10198611884351.08A-1136627324331.48242512104352.03A-12242614524362.44A-13242614524362.44A-14231613864359.60A-15231613864359.60A-16231613864359.60A-17231。

19、613864359.60A-18198611884351.08A-19242612104352.0326425284322.70A-20242614524362.44A-21253615184365.27A-22253615184365.27A-23242614524362.44A-24198611884351.08A-25198611884351.08A-2648729744341.88187611224348.25A-27187611224348.25A-28231613864359.60A-29242614524362.44A-30220613204356.76A-31231613864359.60A-32209612544353.92A-3321624324318.58176610564345.41续上表楼编号单层面积A(㎡)层数建筑面积A(㎡)采暖热指标q(W/㎡)热负荷Qh(k。

20、w)A-34187611224348.25A-35220511004347.30A-36220613204356.76A-37231613864359.60A-38176610564345.41A-39209612544353.92A-40176610564345.41A-4135713574315.35198611884351.08A-42198611884351.08A-43198611884351.08A-44209612544353.92A-45209612544353.92A-46231613864359.60A-47220613204356.76A-48198611884351.08A-4928812884312.3816569904342.57A-50198611884351.08A-51231613864359.60A-52231613864359.60A-53242614。

21、524362.44A-54198611884351.08A-55287617224374.05A-56287617224374.05A-57198611884351.08A-58242614524362.44A-59220613204356.76A-60220613204356.76A-61220613204356.76A-62187611224348.25A-63187611224348.25A-64220613204356.76A-65198611884351.08A-66198611884351.08B-1234614044360.37B-2273616384370.43B-3247614824363.73续上表楼编号单层面积A(㎡)层数建筑面积A(㎡)采暖热指标q(W/㎡)热负荷。管段局部阻力部件个数当量长度总当量长度∑LdZ1-Z2分流三通12.222.222.75异径接头10.。

22、130.13弯头10.40.4J支路管段编号计算流量G'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)12 34568910J-J127.91 1724.5841.581250.6647.61979.21 J1-J225.85 54.49.41250.6140.8383.52 J2-J323.54 1416.930.91250.5633.551036.70 J3-J421.12 53.38.31000.7887.3724.59 J4-J518.46 143.7417.741000.6867.121190.71 J5-J616.27 73.310.31000.6452.65542.30 J6-J714.08 3010.4540.45800.7783.33369.49 J7-J812.12 52.557.55。

23、800.6681.7616.84 J8-J99.81 1510.725.7800.5453.41372.38 J9-J107.62 51.66.6650.5880528.00 J10-J112.94 142.4916.49500.4368.341126.93 资用压力14072.19作用压力12948.71 不平衡率0.08 管段局部阻力部件个数当量长度总当量长度∑LdJ-J1分流三通14.44.424.58截止阀118.518.5弯头11.681.68J1-J2直流三通14.44.44.4J2-J3直流三通14.44.416.9方形补偿器112.512.5J3-J4直流三通13.33.33.3J4-J5直流三通13.33.33.74异径接头10.440.44J5-J6直流三通13.33.33.3J6-J7直流三通12.552.5510.45方形补偿器17.97.9J7-J8直流三通12.。

24、552.552.55续下表续上表管段局部阻力部件个数当量长度总当量长度∑LdJ8-J9直流三通12.552.5510.7异径接头10.330.33方形补偿器17.97.9J9-J10直流三通11.61.61.6J10-J11分流三通11.961.962.49异径接头10.130.13弯头10.130.13H支路管段编号计算流量G'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)1234568910H-H124.761216.828.81250.9120.83479.04H1-H222.9163.39.31250.85104.8974.64H2-H320.721612.128.11250.7887.32453.13H3-H418.5363.749.741000.6867.85660.86H4-H515.761。

25、513.128.1800.59140.53948.05H5-H613.80272.5529.55800.77111.33288.92H6-H711.84102.8812.88800.64579.061018.29H7-H89.77112.5513.55800.5353.46724.38H8-H97.4151.836.83650.5880546.40H9-H105.15117.618.6650.39547874.20H10-H112.85132.0915.09500.4163.8962.74资用压力21482.52作用压力18930.65不平衡率0.12管段局部阻力部件个数当量长度总当量长度∑LdH-H1直流三通13.33.316.8截止阀113.513.5H1-H2直流三通13.33.33.3H2-H3直流三通13.33.312.1方形补偿器19.89.8H3-H4直流三通13.33.33。

26、.74异径接头10.440.44H4-H5直流三通13.33.313.1方形补偿器19.89.8H5-H6直流三通12.552.552.55H6-H7直流三通12.552.552.88异径接头10.330.33续下表续上表管段局部阻力部件个数当量长度总当量长度∑LdH7-H8直流三通12.552.552.55H8-H9直流三通11.51.51.83异径接头10.230.23H9-H10直流三通11.61.67.6方形补偿器166H10-H11直流三通11.961.962.09异径接头10.130.13弯头10.40.4I支路管段编号计算流量G'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)1234568910I-I129.691522.937.91250.753.622032.20I1-I227.8344。

27、.48.41250.6546.94394.30I2-I326.081216.928.91250.6141.11187.79I3-I424.3264.410.41250.5835.87373.05I4-I522.27154.419.41250.5330.21586.07I5-I620.12613.1419.141000.7479.31517.80I6-I718.13213.324.31000.6664.21560.06I7-I815.99174.2821.281000.5950.71078.90I8-I913.74442.2546.25800.75106.264914.53I9-I1011.502310.7833.78800.6375.12536.88I10-I119.44132.5515.55800.5251.3797.72I11-I127.3091.8310.83650.5880866.。

28、40I12-I135.64101.611.6650.4344.6517.36I13-I142.57242.4926.49500.3752.31385.43资用压力20654.63作用压力19748.47不平衡率0.04管段局部阻力部件个数当量长度总当量长度∑LdI-I1直流三通14.44.422.9截止阀118.518.5I1-I2直流三通14.44.44.4I2-I3直流三通14.44.416.9方形补偿器112.512.5I3-I4直流三通13.33.34.4I4-I5直流三通13.33.34.4 续下表续上表管段局部阻力部件个数当量长度总当量长度∑LdI5-I6直流三通13.33.313.14方形补偿器19.89.8异径接头10.440.44I6-I7直流三通13.33.33.3I7-I8直流三通13.33.34.28弯头10.980.98I8-I9直流三通12.552.552.55。

29、I9-I10直流三通12.552.5510.78方形补偿器17.97.9异径接头10.330.33I10-I11直流三通12.552.552.55I11-I12直流三通11.61.61.83异径接头10.230.23I12-I13直流三通11.61.61.6I13-I14直流三通11.961.962.49弯头10.40.4异径接头10.130.13G-K8支路管段编号计算流量G'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)12 34568910G-K199.00 2733602000.8341.482488.8K1-K212.79 1712.7529.75800.793.022767.35 K2-K311.23 52.557.55800.6271.26538.01 K3-K49.27 101.8311.。

30、83650.72123.061455.80 K4-K57.42 97.616.6650.58801328.00 K5-K65.37 101.611.6650.4241.5481.40 K6-K74.01 131.114.1500.59126.61785.06 K7-K82.05 192.3621.36500.3134.3732.65 资用压力24688.72作用压力11701.51 不平衡率0.53 管段局部阻力部件个数当量长度总当量长度∑LdG-K1分流三通124.624.633方形补偿器18.48.4K1-K2分流三通12.552.5512.75截止阀110.210.2K2-K3直流三通12.552.552.55续下表续上表管段局部阻力部件个数当量长度总当量长度∑LdK3-K4直流三通11.61.61.83异径接头10.230.23K4-K5直流三通11.61.67.6方形补偿器166。

31、K5-K6直流三通11.61.61.6K6-K7直流三通10.970.971.1异径接头10.130.13K7-K8分流三通11.961.962.36弯头10.40.4G-M10支路管段编号计算流量G'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)12 34568910G-K199.00 2733602000.8341.482488.8N1-M086.21 78.415.42000.7635.08540.232M0-M125.53 2416.840.81000.94128.855257.08 M1-M223.34 53.38.31000.86107.59893.00 M2-M321.03 1412.126.11000.7887.32278.53 M3-M418.84 53.38.31000.6969.68。

32、578.34 M4-M516.64 123.315.31000.5754.6835.38 M5-M614.45 52.887.88800.8119.1938.51 M6-M712.14 3210.4542.45800.6681.73468.17 M7-M89.14 71.68.6650.7115.2990.72 M8-M96.26 111.8312.83650.4854.7701.80 M9-M102.77 152.4917.49500.4160.681061.29 资用压力24688.72作用压力20265.73 不平衡率0.18 管段局部阻力部件个数当量长度总当量长度∑LdG-K1分流三通124.624.633方形补偿器18.48.4M0-M1直流三通13.33.316.8截止阀113.513.5M1-M2直流三通13.33.33.3M2-M3直流三通13.33.312.1方形补偿器1。

33、9.89.8M3-M4直流三通13.33.33.1M4-M5直流三通13.33.33.3续下表续上表管段局部阻力部件个数当量长度总当量长度∑LdM5-M6直流三通12.552.552.88异径接头10.330.33M6-M7直流三通12.552.5510.45方形补偿器17.97.9M7-M8直流三通11.61.61.6M8-M9直流三通11.61.61.83异径接头10.230.23M9-M10直流三通11.961.962.49异径接头10.130.13弯头10.40.4G-N19支路管段编号计算流量G'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)12 34568910G-K199.00 2733602000.8341.482488.8N1-M086.21 78.415.42000.7635.0854。

34、0.232MO-N160.68 698.477.41500.9883.46455.16N1-N235.30 1322.935.91250.8175.692717.271N2-N333.54 114.415.41250.7968.251051.05N3-N431.78 64.410.41250.7561.44638.976N4-N529.24 1016.926.91250.6951.821393.958N5-N627.48 114.415.41250.6512.95199.43N6-N724.93 74.8411.841250.5937.9448.736N7-N822.94 1116.927.91250.5735976.5N8-N921.19 73.310.31000.889916.7N9-N1019.53 203.323.31000.7275.41756.82N10-N1117.38 11。

35、3.314.31000.6460858N11-N1215.72 1013.123.11000.5748.871128.897N12-N1313.67 92.8811.881000.536.1428.868N13-N1411.68 132.5515.55800.6577.741208.857N14-N159.69 72.559.55800.5453.46510.543N15-N167.66 127.8319.83650.6186.761720.451N16-N175.67 91.610.6650.4547.8506.68N17-N183.91 81.839.83650.322.2218.226N18-N191.89 182.3620.36500.2829.5600.62资用压力24688.72作用压力26884.11 不平衡率-0.09 管段局部阻力部件个数当量长度总当量长度∑LdN5-N6。

36、直流三通14.44.44.4N6-N7直流三通14.44.44.84异径接头10.440.44N7-N8直流三通14.44.416.9方形补偿器112.512.5N8-N9直流三通13.33.33.3N9-N10直流三通13.33.33.3N10-N11直流三通13.33.33.3N11-N12直流三通13.33.313.1方形补偿器19.89.8N12-N13直流三通13.33.33.56异径接头10.260.26N13-N14直流三通12.552.552.55N14-N15直流三通12.552.552.55N15-N16直流三通11.61.67.83方形补偿器166异径接头10.230.23N16-N17直流三通11.61.6 N17-N18直流三通11.61.61.83异径接头10.230.23N18-N19直流三通11.961.962.36弯头10.40.4F支路管段编号计算流量G。

37、'(t/h)管段长度L(m)当量长度Ld(m)折算长度Lzh(m)工称直径d(m)流速v(m/s)比摩阻R(Pa/m)压损△P(Pa)12 34568910F-F19.51 4019.4359.431000.7479.34712.80 F1-F27.64 2112.27533.275650.5983.382774.47 F2-F35.80 172.5519.55650.4547.8934.49 F3-F44.04 206.6326.63500.59126.63371.36 F4-F52.29 352.3637.36500.3441.81561.65 资用压力32270.49作用压力13354.76 不平衡率0.59 管段局部阻力部件个数当量长度总当量长度∑LdF-F1分流三通14.954.9519.43截止阀113.513.5弯头10.980.98 续下续上表管段局部阻力部件个数当量长度总当量长度∑LdF1-F2直流三通12.552.5512.275异径接头11.8251.825方形补偿器17.97.9F2-F3直流三通12.552.552.55F3-F4直流三通11.31.36.63异径接头10.130.13方形补偿器15.25.2F4-F5分流三通11.961.962.36弯头10.40.4。

关 键 词:
小区 设计 供热 管网
 ope平台t所有资源均是用户自行上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作他用。
关于本文
本文标题:某市某小区供热管网及换热站设计.doc
链接地址: /s-62276226.html
关于我们 - 网站声明 - 网站地图 - 资源地图 - 友情链接 - 网站客服点击这里,给ope平台t发消息,QQ:3074922707 - 联系我们

本站为“文档C2C交易模式”,即用户上传的文档直接卖给(下载)用户,本站只是中间服务平台,本站所有文档下载所得的收益归上传人(含作者)所有【成交的100%(原创)】。本站是网络服务平台方,若您的权利被侵害,侵权客服QQ:3074922707 欢迎举报。

3074922707@qq.com 2017-2027 网站版权所有

 

收起
展开